| Charging Instructions |
| 1. |
Always recharge the battery after use. |
2.
|
Constant voltage charging is recommended. At 25°C, 2.25-2.30 vpc for float use and 2.40-2.45 vpc for cycle use. |
3.
|
The maximum initial charging current should be 0.3CA. |
4.
|
If batteries are used in series or parallel, the correct size cabling should be used. |
| 5. |
The battery requires approx. 110% of the total discharging energy to fully recharge. |
| |
|
| Discharging Instructions |
1.
|
Never leave a battery in a discharging condition. |
2.
|
Never allow a battery to fall below 2 vpc in storage. The full capacity may not be able to be restored and actual service life decreased. |
3.
|
Maximum continuous discharge current is 3C. For greater continuous discharge currents please consult our technical staff. |
4.
|
Discharge currents of less than 1 CA should be used. |
| 5. |
Stored batteries should receive a supplementary charge at intervals suggested. See chart. |